Specifications: Driver Module
Supply voltage 85 to 264V ac
Supply freqeuncy 47 to 63Hz
Power consumption 120W
Temperature limits 0 to 50°C operating, -10 to 70°C storage
Display 4 lines dot LCD matrix array
Communications Modbus RTU 2 wire EIA485
Modbus TCP/IP 10baseT
Ethernet, Profibus DPv1, DeviceNet network protocol
Inputs and outputs:
standard
2 analogue inputs, 1 analogue output, 2 digital inputs,
2 relay outputs (1=Watchdog)
Optional modules (max 3) Per module - 1 analogue input, 1 analogue output, 2 digital inputs, 1 relay
Measurement accuracy Better than 1%
Remote panel Dedicated remote panel port
32h8e panel indicator
Quickstart Configurable by order code or on start up via dedicated front panel HMI
Predictive load management (PLM) Optional module connecting up to 63 instruments over dedicated communications (CAN based). Configurable PLM (patent pending) optimises energy usage.
Approvals CE (EN 60947-4-3), UL 508A


Click here for power module specification.
PDF Click for Eurotherm thyristor manuals
PDF Click for Eurotherm thyristor data sheets
Full ordering codes avaliable on product data sheet - PDF small Direct link to PDF data sheet (Opens in new window/tab)
If you require futher assistance please contact our office.